JC Lead-Calcium Standby Batteries
For
telecommunications, switchgear, and control applications
Capacities from 50 to 300 Ampere-hours
|
|
FEATURES AND BENEFITS
-
Increased jar-cover seal area for added
reliability
-
Enhanced leak-proof epoxy post seal for reduced
maintenance and added reliability
-
Cost-effective answer to today's small-power
applications
-
Four-cell design offers reduced length for optimum
space utilization (shorter racks)
-
Fewer bolted connectors per battery string for
reduced installation and maintenance costs
-
Low-maintenance, lead-calcium alloy for extended
watering intervals
-
Flame-retardant covers for enhanced battery plant
safety
-
Two-point, top-suspended positive plates permit
free growth without pressure on jar and cover for
reliable service life
-
Snap-On, intercell-connector covers for safety
-
Terminals accessible for measurement of individual
cell voltages for convenience and easy data
collection
-
Low-evaporation, flame-arrester vent with flip-top
dust cover for safety
|
|
Plates |
Height
|
Width
|
Thickness
|
|
Positive
Negative
Outside negative
|
8.00 in (203 mm)
8.00 in (203 mm)
8.00 in (203 mm) |
7.62 in (194 mm)
7.62 in (194 mm)
7.62 in (194 mm) |
0.250 in (6.40 mm)
0.165 in (4.19 mm)
0.120 in (3.05 mm) |
|
Electrolyte height above plates |
2.70 in (69mm) |
|
Sediment space |
0.88 in (22mm) |
|
Electrolyte @ 77F (25C) |
Sulfuric acid, 1.215 specific gravity nominal |
|
Float voltages |
2.19-2.21 volts per cell |
|
Container † |
Thermoplastic, transparent, polycarb and SAN available |
|
Cover |
High-impact, flame-retardant thermoplastic with
tongue-and-groove seal.
Flammability ratings: UL 94-VO; ASTM D-635
self-extinguishing |
|
Separator |
Microporous with fibrous glass mat |
|
Safety vent system |
Flame-arrester/low-evaporation type with flip-top dust
cover |
|
Terminals |
Cast-lead alloy (chair type) |
Options
†Container |
Transparent, flame-retardant polycarbonate, oxygen
index of 26.
Flammability ratings: UL 94-HB; ASTM D-635-68,
self-extinguishing |
|
Special voltages |
Modules with dummy cells are available |
|
Final volts
|
Models
|
Nominal rates at 77F (25C)
(includes connector voltage drop)
|
|
Ampere-hours
|
Amperes
|
|
8 Hr
|
5 Hr
|
3 Hr
|
1.5 Hr
|
1 Hr
|
30 Min
|
15 Min
|
1 Min
|
|
1.84
|
4JC-50
4JC-100
4JC-150
2JC-200
2JC-300
|
47
94
141
188
282
|
41
82
123
164
246 |
34
68
102
136
203
|
26
52
78
104
156
|
21
42
63
84
126 |
28
56
84
112
168
|
34
68
102
136
204 |
44
88
132
176
264
|
|
1.81
|
4JC-50
4JC-100
4JC-150
2JC-200
2JC-300
|
48
96
144
192
288
|
42
84
125
167
251
|
35
71
106
142
212
|
27
54
81
108
162
|
23
46
69
92
138
|
31
62
93
124
186
|
39
78
117
156
234
|
51
102
153
204
306
|
|
1.78
|
4JC-50
4JC-100
4JC-150
2JC-200
2JC-300
|
49
98
147
196
294
|
43
87
130
173
260
|
37
74
110
147
221
|
29
57
86
114
171
|
24
48
72
96
144
|
34
68
102
136
204
|
43
86
129
172
258
|
59
118
177
236
354
|
|
1.75
|
4JC-50
4JC-100
4JC-150
2JC-200
2JC-300
|
50
100
150
200
300
|
44
88
132
176
264
|
38
76
114
152
228
|
30
60
90
120
180
|
26
52
78
104
156
|
36
72
108
144
216
|
47
94
141
188
282
|
68
135
203
270
405
|
|
Note: |
Data based on discharge from a minimum of 72 hours on
float at 77F (25C)
in accordance with IEEE-450. |
|
Models
|
Cells
per unit
|
Plates
per cell
|
Overall dimensions
|
Approx. wt.
lbs (kgs)
|
Electrolyte
per cell
lbs (kgs)
|
Pure
sulfuric acid
per cell
lbs (kgs)
|
|
L
in (mm)
|
W
in (mm)
|
H
in (mm)
|
Net
filled
|
Dom.
packed
|
|
4JC-50
|
Four cells connected
in series for
eight-volt units |
3 |
10.27
(261)
|
10.0
(254)
|
14.6
(371)
|
78
(35.4)
|
84
(38.1)
|
8.2 (3.7)
|
2.4 (1.1)
|
|
4JC-100
|
5
|
94
(42.6)
|
100
(45.4)
|
7.1 (3.2)
|
2.1 (.95)
|
|
4JC-150
|
7
|
110
(50)
|
116
(52.6)
|
6.0 (2.7)
|
1.8 (.81)
|
|
2JC-200
|
Four cells connected
in series/parallel
for four-volt unit
|
2x5
|
94
(42.6)
|
100
(45.4)
|
7.1 (3.2)
|
2.1 (.95)
|
|
2JC-300
|
2x7
|
110
(50)
|
116
(52.6)
|
6.0 (2.7)
|
1.8 (.81)
|
|
Notes:
|
Electrolyte weighs approximately 10 lbs per gallon
(1.215 kg/ liter). |
|