TEL:
415-242-1551 |
| |
Batteries
| |
|
4LCY LEAD-CALCIUM
For
switchgear applications
Capacities from 285 to 646 Ampere-hours
|
|
Features and Benefits
-
Vacuum-assisted, bottom-pour, positive grid casting
assures plate quality and long life
-
Four-cell design offers reduced length for optimum
space utilization (shorter racks)
-
Flame-retardant covers enhance battery plant safety
-
Suspended positive plate permits free growth without
pressure on jar and cover
-
Snap-on, intercell-connector-insulating covers
-
Terminals accessible for measurement of individual
cell voltages
-
Transparent container allows visual inspection of
plates
-
Electrical testing to 100 percent capacity assures
performance of every battery
|
|
Plates |
Height
|
Width
|
Thickness
|
|
Positive |
15 in (381 mm)
|
12 in (305 mm)
|
0.250 in (6.4 mm)
|
|
Negative |
15 in (381 mm)
|
12 in (305 mm)
|
0.180 in (4.6 mm)
|
|
Outside negative |
15 in (381 mm)
|
12 in (305 mm)
|
0.130 in (3.3 mm)
|
|
Electrolyte height above plates |
2.88 in (73 mm) |
|
Sediment space |
0.63 in (16 mm) |
|
Electrolyte @ 77F (25C) |
Sulfuric acid, 1.215 specific gravity nominal |
|
Float voltages |
2.20-2.25 volts per cell |
|
Container† |
Thermoplastic, transparent |
|
Cover |
High-impact, flame-retardant thermoplastic (PVC) with
tongue-and-groove seal
Flammability ratings: UL94-VO; LOI>33; ASTM D-635
self-extinguishing |
|
Separator |
Microporous with fibrous glass mat |
|
Safety vent system |
Flame-arrester type with dust cover |
Terminals
4LCY-5 and 7
4LCY-9 and 11 |
Two, 0.5 in (12.7 mm) x
1.38 in (35.1 mm)
cast-lead terminals
Two, 1 in (25 mm) square
posts per unit |
|
Withdrawal tubes |
One
per cell |
|
†Optional Container |
Transparent, flame-retardant polycarbonate
Flammability ratings: UL 94-HB; ASTM D-635
self-extinguishing |
|
Special voltages |
Models with dummy cells are available |

|
4LCY 1.215 SG 77°F CONNECTOR DROP INCLUDED
|
|
|
Capacity correction factor
|
|
Battery
|
1
Min
|
15 Min
|
30 Min
|
60 Min
|
180 Min
|
480 Min
|
|
4LCY-5
|
1.04
|
1.02
|
1.04
|
1.10
|
1.10
|
1.10
|
|
4LCY-7
|
1.03
|
1.02
|
1.04
|
1.06
|
1.06
|
1.06
|
|
4LCY-9
|
1.01
|
1.00
|
1.02
|
1.03
|
1.03
|
1.03
|
|
4LCY-11
|
1.00
|
1.00
|
1.00
|
1.00
|
1.00
|
1.00
|
To
convert rates from 1.215 to 1.250, multiply the printed
rate by 10 percent.
Data based on discharge from float at 77F (25C) for a
minimum of 72 hours.
|
Type of
battery
|
Cells
per unit
|
Plates
per cell
|
Nominal cap. to 1.75 avg.
Vpc @ 77F (25C)
(Includes
connector voltage drop)*
|
Overall
Dimensions
|
Approx. wt.
lbs. (kgs)
|
Electrolyte
per cell
lbs (kgs)
|
|
Ampere-hours
|
Amperes
|
L in (mm)
|
W in (mm)
|
H in (mm)
|
Net filled
|
Dom. packed
|
|
8 Hr
|
3 Hr
|
1 Hr
|
30 Min
|
15 Min
|
1 Min
|
|
4LCY-5
|
4
|
5
|
285
|
218
|
146
|
201
|
262
|
386
|
10.08 (256)
|
14.12 (359)
|
22.75 (578)
|
253 (114.8)
|
288 (121.6)
|
20 (9.1)
|
|
4LCY-7
|
4
|
7
|
411
|
313
|
212
|
302
|
392
|
574
|
10.08 (256)
|
310 (140.6)
|
325 (147.4)
|
18 (8.2)
|
|
4LCY-9
|
4
|
9
|
532
|
407
|
274
|
393
|
516
|
750
|
15.00 (381)
|
395 (179.2)
|
415 (188.2)
|
25 (11.3)
|
|
4LCY-11
|
4
|
11
|
646
|
494
|
332
|
484
|
644
|
929
|
15.00 (381)
|
450 (204.1)
|
470 (213.2)
|
23 (10.4)
|
|
Notes:
|
Electrolyte weighs approximately 10 lbs per gallon
(1.210 kgs per liter).
* Data based on discharge from float at 77F (25C)
for a minimum of 72 hours.
|
|
Battery
|
|
Two-step
Model RDB-903-(L)
Width: 44.8 in (1138 mm)
Height: 52.3 in (1329
mm)
|
|
|
|
TWO-TIER
Model RDB-901-(L)
Width: 24.0 in (611
mm)
Height: 65.8 in (1672
mm)
|
|
|
|
THREE-TIER
Model RDB-902-(L)
Width: 25.0 (637 mm)
Height: 94.8 in (2408
mm)
|
|
|
|
Length (L)
|
Weight
|
No.
req'd.
|
Length (L)
|
Weight
|
No.
req'd.
|
Length (L)
|
Weight
|
No.
req'd.
|
|
ft
|
mm
|
lbs
|
kg
|
ft
|
mm
|
lbs
|
kg
|
ft
|
mm
|
lbs
|
kg
|
|
60-CELL BATTERY
|
|
4LCY-5
4LCY-7
|
7
|
2134
|
285
|
130
|
1
|
7
|
2134
|
280
|
127
|
1
|
5
|
1524
|
265
|
120
|
1
|
|
4 LCY-9
4LCY-11
|
11
|
3353
|
400
|
182
|
1
|
11
|
3353
|
380
|
173
|
1
|
7
|
2134
|
400
|
182
|
1
|
|
Notes:
|
1.
|
For information on racks, see brochure 12-560. |
| |
2.
|
Rack lengths for other than 60-cell batteries can
be calculated by the formula: Number of cells per
tier or step x (L + 0.5) - 0.5 = total rack
length.
(Where "L" is length of cell.) Where dimensions
are critical, check with C&D engineering.
|
| |
3.
|
Rack width does not include thickness of
crossbracing; increase width by 0.5 in. (12.7
mm) for crossbracing when this dimension is
critical.
|
| |
4.
|
Height measured from base to top terminal of upper
tier battery.
|
|
| |
|
|
|
| |
|